Operations console

Customers

Pak Agro Farms - Unit 1

25.0 kW On-Grid system in Karachi, commissioned 10 Nov 2022

System health

50

Performance ratio against baseline, less open defects

Generated (30 days)

2.4 MWh

86% of expected

Modelled soiling loss

11.9%

Last cleaned 27 May 2026

Performance ratio

71.5%

Baseline 83%, target 82%

Generation, expected against actual

Ninety days. The dashed line is the design expectation; the gap between the lines is money.

Soiling loss

Climbs between washes, drops sharply after rain or a clean. The dashed line is the point where a cleaning visit pays for itself.

Performance ratio trend

Against the fleet target.

System specification
Capacity
25.0 kW
System type
On-Grid
Modules
46 x 545W Canadian Solar
Inverter
Solis S6-GR1P-25K (22.5 kW)
Battery
None
Tilt / azimuth
27 deg / 170 deg
Bird mesh
Not installed
Tariff
Rs 45 per kWh
Net metering
Approved
NM reference
NM-2025-93840
Sanctioned
25 kW
AMC
Commercial Pro
Open findings

Unresolved defects on this site.

  • Hotspot detected on string B

    Critical

    Thermal scan shows a cell running 27 degrees above array average. Bypass diode failure suspected.

  • Bird nesting under array

    Minor

    Pigeons nesting between modules and roof. Bird mesh recommended for the full perimeter.

  • Inverter derating in afternoon peak

    Major

    Unit throttles above 46 degrees ambient. Cooling fins clogged with dust.

  • Warranty documents missing

    Info

    Module warranty pack not on file. Copies requested from the original installer.

  • Burnt MC4 connector

    Critical

    DC connector on string C shows arcing damage. Replaced on site and adjacent connectors re-terminated.

  • Heavy soiling on lower rows

    Minor

    Dust accumulation reducing output on the two lowest rows more than the rest of the array.

Work order history

6 visits

CodeServiceStatusAmount
JOB-2026-0037School & Hospital Solar MaintenanceScheduledRs 24.0K
JOB-2026-0032Performance OptimizationCompletedRs 23.8K
JOB-2026-0151Wiring Inspection & RepairCompletedRs 8.2K
JOB-2026-0165Performance TestingInvoicedRs 9.0K
JOB-2026-0169Cable ReplacementCompletedRs 12.2K
JOB-2026-0137Junction Box RepairInvoicedRs 4.5K
Inspection reports