System Health Audit

RPT-2026-017 - performed 16 Mar 2026 by Waqar Ahmed

Health score

97

Measurements taken

6

1 outside reference

Findings

2

Customer visibility

Shared

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)752 VWithin 5% of designPass
Short circuit current (string A)8.6 AWithin 8% of nameplatePass
Earth electrode resistance7.2 ohmBelow 5 ohmOutside reference
Insulation resistance (DC+ to earth)7 MohmAbove 1 MohmPass
Max module temperature47 CBelow 25 C above ambientPass
Performance ratio on test day74%Baseline 83%Pass
Context
Capacity
25.0 kW
Work order
JOB-2026-0169
Technician
Waqar Ahmed
Recommendation

System is healthy. Continue the current cleaning cycle and re-inspect in six months.

Score 97 / 100
Findings

Defects recorded during this inspection.

  • Burnt MC4 connector

    CriticalOpen

    DC connector on string C shows arcing damage. Replaced on site and adjacent connectors re-terminated.

  • String mismatch on MPPT 2

    MajorResolved

    String currents differ by 18 percent, pointing to partial shading or module degradation.