Operations console

All work orders

Technical Reports

JOB-2026-0129 - raised via Phone 4 mo ago

InvoicedNormal priorityCommercial Pro AMC
Checklist

6 of 6 steps complete

Findings

Defects recorded on site. Unresolved criticals roll up to the operations overview.

  • Earthing resistance above limit

    Major

    Measured 9.4 ohm against a 5 ohm reference. Earth pit needs re-treatment.

    Open

  • String mismatch on MPPT 2

    Major

    String currents differ by 18 percent, pointing to partial shading or module degradation.

    Open

Parts used

Consumed from van stock on this visit.

No parts consumed

Result

Generation either side of the visit.

+45 kWhper day

177 kWh before, 222 kWh after

Worth about Rs 54,000 a month at this site's tariff.

Assignment

Technician

Asif Mehmood
Details
City
Lahore
Capacity
60.0 kW
Raised
27 Apr 2026, 10:00 AM
Scheduled
27 Apr 2026, 1:00 PM
SLA due
27 Apr 2026, 6:00 PM (4 mo ago)
Completed
27 Apr 2026, 1:00 PM
Services
Technical Reports
Amount
Rs 6,500