Operations console
All reports
Thermal Camera Inspection
RPT-2026-026 - performed 2 May 2026 by Junaid Khan
Health score
61
Measurements taken
6
1 outside reference
Findings
1
Customer visibility
Internal only
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 779 V | Within 5% of design | Pass |
| Short circuit current (string A) | 12.2 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 2.4 ohm | Below 5 ohm | Pass |
| Insulation resistance (DC+ to earth) | 80 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 51 C | Below 25 C above ambient | Pass |
| Performance ratio on test day | 67% | Baseline 85% | Outside reference |
Context
- Customer
- Pak Agro Farms
- Capacity
- 60.0 kW
- Work order
- JOB-2026-0110
- Technician
- Junaid Khan
Recommendation
Schedule corrective repair within 14 days. Losses at the current rate exceed the cost of the fix.
Score 61 / 100Findings
Defects recorded during this inspection.
No defects found
InfoResolvedSystem operating within expected parameters on the day of inspection.