Operations console

All reports

Thermal Camera Inspection

RPT-2026-026 - performed 2 May 2026 by Junaid Khan

Health score

61

Measurements taken

6

1 outside reference

Findings

1

Customer visibility

Internal only

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)779 VWithin 5% of designPass
Short circuit current (string A)12.2 AWithin 8% of nameplatePass
Earth electrode resistance2.4 ohmBelow 5 ohmPass
Insulation resistance (DC+ to earth)80 MohmAbove 1 MohmPass
Max module temperature51 CBelow 25 C above ambientPass
Performance ratio on test day67%Baseline 85%Outside reference
Context
Capacity
60.0 kW
Work order
JOB-2026-0110
Technician
Junaid Khan
Recommendation

Schedule corrective repair within 14 days. Losses at the current rate exceed the cost of the fix.

Score 61 / 100
Findings

Defects recorded during this inspection.

  • No defects found

    InfoResolved

    System operating within expected parameters on the day of inspection.