Electrical Safety Audit
RPT-2026-024 - performed 12 Jul 2026 by Waqar Ahmed
Health score
94
Measurements taken
6
0 outside reference
Findings
2
Customer visibility
Shared
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 661 V | Within 5% of design | Pass |
| Short circuit current (string A) | 8.5 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 6.2 ohm | Below 5 ohm | Pass |
| Insulation resistance (DC+ to earth) | 7 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 71 C | Below 25 C above ambient | Pass |
| Performance ratio on test day | 86% | Baseline 85% | Pass |
Context
- Customer
- Pak Agro Farms
- Capacity
- 60.0 kW
- Work order
- JOB-2026-0024
- Technician
- Waqar Ahmed
Recommendation
System is healthy. Continue the current cleaning cycle and re-inspect in six months.
Score 94 / 100Findings
Defects recorded during this inspection.
Loose structure bolt
MinorOpenTwo mid-clamps below torque specification on the north row. Retorqued.
Heavy soiling on lower rows
MinorResolvedDust accumulation reducing output on the two lowest rows more than the rest of the array.