Operations console

All reports

Electrical Safety Audit

RPT-2026-024 - performed 12 Jul 2026 by Waqar Ahmed

Health score

94

Measurements taken

6

0 outside reference

Findings

2

Customer visibility

Shared

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)661 VWithin 5% of designPass
Short circuit current (string A)8.5 AWithin 8% of nameplatePass
Earth electrode resistance6.2 ohmBelow 5 ohmPass
Insulation resistance (DC+ to earth)7 MohmAbove 1 MohmPass
Max module temperature71 CBelow 25 C above ambientPass
Performance ratio on test day86%Baseline 85%Pass
Context
Capacity
60.0 kW
Work order
JOB-2026-0024
Technician
Waqar Ahmed
Recommendation

System is healthy. Continue the current cleaning cycle and re-inspect in six months.

Score 94 / 100
Findings

Defects recorded during this inspection.

  • Loose structure bolt

    MinorOpen

    Two mid-clamps below torque specification on the north row. Retorqued.

  • Heavy soiling on lower rows

    MinorResolved

    Dust accumulation reducing output on the two lowest rows more than the rest of the array.