Operations console

All reports

Insulation Resistance Testing

RPT-2026-022 - performed 29 Apr 2026 by Asif Mehmood

Health score

60

Measurements taken

6

1 outside reference

Findings

3

Customer visibility

Shared

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)751 VWithin 5% of designPass
Short circuit current (string A)9.5 AWithin 8% of nameplatePass
Earth electrode resistance5.3 ohmBelow 5 ohmPass
Insulation resistance (DC+ to earth)2 MohmAbove 1 MohmPass
Max module temperature50 CBelow 25 C above ambientPass
Performance ratio on test day81%Baseline 83%Outside reference
Context
Capacity
32.0 kW
Work order
JOB-2026-0060
Technician
Asif Mehmood
Recommendation

Schedule corrective repair within 14 days. Losses at the current rate exceed the cost of the fix.

Score 60 / 100
Findings

Defects recorded during this inspection.

  • Heavy soiling on lower rows

    MinorResolved

    Dust accumulation reducing output on the two lowest rows more than the rest of the array.

  • Monitoring app not configured

    InfoResolved

    Customer has no visibility of live generation. App setup offered.

  • Bird nesting under array

    MinorResolved

    Pigeons nesting between modules and roof. Bird mesh recommended for the full perimeter.