Earthing Resistance Testing

RPT-2026-021 - performed 10 May 2026 by Faisal Shahzad

Health score

60

Measurements taken

6

3 outside reference

Findings

2

Customer visibility

Shared

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)658 VWithin 5% of designPass
Short circuit current (string A)8.4 AWithin 8% of nameplatePass
Earth electrode resistance9.3 ohmBelow 5 ohmPass
Insulation resistance (DC+ to earth)35 MohmAbove 1 MohmOutside reference
Max module temperature66 CBelow 25 C above ambientOutside reference
Performance ratio on test day80%Baseline 79%Outside reference
Context
Capacity
200.0 kW
Work order
JOB-2026-0052
Technician
Faisal Shahzad
Recommendation

Schedule corrective repair within 14 days. Losses at the current rate exceed the cost of the fix.

Score 60 / 100
Findings

Defects recorded during this inspection.

  • String mismatch on MPPT 2

    MajorOpen

    String currents differ by 18 percent, pointing to partial shading or module degradation.

  • Warranty documents missing

    InfoOpen

    Module warranty pack not on file. Copies requested from the original installer.