String Testing
RPT-2026-020 - performed 6 Mar 2026 by Danish Ali
Health score
65
Measurements taken
6
2 outside reference
Findings
1
Customer visibility
Shared
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 703 V | Within 5% of design | Pass |
| Short circuit current (string A) | 12 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 5.9 ohm | Below 5 ohm | Outside reference |
| Insulation resistance (DC+ to earth) | 61 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 72 C | Below 25 C above ambient | Pass |
| Performance ratio on test day | 78% | Baseline 83% | Outside reference |
Context
- Site
- Nadia Rehman
- Customer
- Nadia Rehman
- Capacity
- 10.0 kW
- Work order
- JOB-2026-0160
- Technician
- Danish Ali
Recommendation
Schedule corrective repair within 14 days. Losses at the current rate exceed the cost of the fix.
Score 65 / 100Findings
Defects recorded during this inspection.
Hotspot detected on string B
CriticalOpenThermal scan shows a cell running 27 degrees above array average. Bypass diode failure suspected.