Operations console
All reports
Thermal Camera Inspection
RPT-2026-018 - performed 19 May 2026 by Faisal Shahzad
Health score
78
Measurements taken
6
1 outside reference
Findings
1
Customer visibility
Internal only
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 678 V | Within 5% of design | Pass |
| Short circuit current (string A) | 10 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 5.3 ohm | Below 5 ohm | Pass |
| Insulation resistance (DC+ to earth) | 24 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 54 C | Below 25 C above ambient | Outside reference |
| Performance ratio on test day | 84% | Baseline 82% | Pass |
Context
- Site
- Rabia Nawaz
- Customer
- Rabia Nawaz
- Capacity
- 12.0 kW
- Work order
- JOB-2026-0105
- Technician
- Faisal Shahzad
Recommendation
Bring cleaning forward by one cycle and re-torque the affected strings within 30 days.
Score 78 / 100Findings
Defects recorded during this inspection.
Heavy soiling on lower rows
MinorResolvedDust accumulation reducing output on the two lowest rows more than the rest of the array.