RPT-2026-015 - performed 14 May 2026 by Danish Ali
Health score
97
Measurements taken
6
1 outside reference
Findings
2
Customer visibility
Internal only
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 578 V | Within 5% of design | Pass |
| Short circuit current (string A) | 10.5 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 2.2 ohm | Below 5 ohm | Pass |
| Insulation resistance (DC+ to earth) | 7 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 49 C | Below 25 C above ambient | Outside reference |
| Performance ratio on test day | 86% | Baseline 83% | Pass |
Context
- Customer
- Crescent Plaza
- Capacity
- 32.0 kW
- Work order
- JOB-2026-0062
- Technician
- Danish Ali
Recommendation
System is healthy. Continue the current cleaning cycle and re-inspect in six months.
Score 97 / 100Findings
Defects recorded during this inspection.
Monitoring app not configured
InfoOpenCustomer has no visibility of live generation. App setup offered.
Earthing resistance above limit
MajorResolvedMeasured 9.4 ohm against a 5 ohm reference. Earth pit needs re-treatment.