Operations console
All reports
Electrical Safety Audit
RPT-2026-008 - performed 1 Mar 2026 by Rizwan Sattar
Health score
80
Measurements taken
6
0 outside reference
Findings
1
Customer visibility
Internal only
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 732 V | Within 5% of design | Pass |
| Short circuit current (string A) | 9.7 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 4 ohm | Below 5 ohm | Pass |
| Insulation resistance (DC+ to earth) | 62 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 66 C | Below 25 C above ambient | Pass |
| Performance ratio on test day | 76% | Baseline 83% | Pass |
Context
- Customer
- Metro Warehousing
- Capacity
- 150.0 kW
- Work order
- JOB-2026-0125
- Technician
- Rizwan Sattar
Recommendation
Bring cleaning forward by one cycle and re-torque the affected strings within 30 days.
Score 80 / 100Findings
Defects recorded during this inspection.
Bird nesting under array
MinorOpenPigeons nesting between modules and roof. Bird mesh recommended for the full perimeter.