Operations console

All reports

String Testing

RPT-2026-004 - performed 27 Apr 2026 by Waqar Ahmed

Health score

97

Measurements taken

6

2 outside reference

Findings

1

Customer visibility

Shared

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)761 VWithin 5% of designPass
Short circuit current (string A)10.3 AWithin 8% of nameplateOutside reference
Earth electrode resistance3.4 ohmBelow 5 ohmPass
Insulation resistance (DC+ to earth)20 MohmAbove 1 MohmOutside reference
Max module temperature53 CBelow 25 C above ambientPass
Performance ratio on test day75%Baseline 81%Pass
Context
Capacity
25.0 kW
Work order
JOB-2026-0072
Technician
Waqar Ahmed
Recommendation

System is healthy. Continue the current cleaning cycle and re-inspect in six months.

Score 97 / 100
Findings

Defects recorded during this inspection.

  • No defects found

    InfoResolved

    System operating within expected parameters on the day of inspection.