System Health Audit
RPT-2026-001 - performed 14 Feb 2026 by Naveed Iqbal
Health score
60
Measurements taken
6
2 outside reference
Findings
1
Customer visibility
Shared
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 631 V | Within 5% of design | Pass |
| Short circuit current (string A) | 9.5 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 3.1 ohm | Below 5 ohm | Outside reference |
| Insulation resistance (DC+ to earth) | 6 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 73 C | Below 25 C above ambient | Pass |
| Performance ratio on test day | 81% | Baseline 79% | Outside reference |
Context
- Site
- Imran Baig
- Customer
- Imran Baig
- Capacity
- 5.0 kW
- Work order
- JOB-2026-0025
- Technician
- Naveed Iqbal
Recommendation
Schedule corrective repair within 14 days. Losses at the current rate exceed the cost of the fix.
Score 60 / 100Findings
Defects recorded during this inspection.
No defects found
InfoResolvedSystem operating within expected parameters on the day of inspection.