Operations console
All reports
System Health Audit
RPT-2026-009 - performed 23 Jun 2026 by Junaid Khan
Health score
79
Measurements taken
6
0 outside reference
Findings
1
Customer visibility
Internal only
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 658 V | Within 5% of design | Pass |
| Short circuit current (string A) | 8.5 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 6 ohm | Below 5 ohm | Pass |
| Insulation resistance (DC+ to earth) | 85 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 55 C | Below 25 C above ambient | Pass |
| Performance ratio on test day | 74% | Baseline 86% | Pass |
Context
- Site
- Fatima Sheikh
- Customer
- Fatima Sheikh
- Capacity
- 15.0 kW
- Work order
- JOB-2026-0155
- Technician
- Junaid Khan
Recommendation
Bring cleaning forward by one cycle and re-torque the affected strings within 30 days.
Score 79 / 100Findings
Defects recorded during this inspection.
Warranty documents missing
InfoOpenModule warranty pack not on file. Copies requested from the original installer.